AJ POWER

Local Application of Generators with High Pressure Watermist.

Fireworks recently designed and installed a Hydramist® high-pressure Watermist fire suppression system which was designed to provide fire protection to the generators for Caterpillar on a site in Sweden. The system was designed to provide local application protection to each of the six generators on site allowing for full deluge fire suppression for all six generators using high pressure watermist cylinders.

This system will be activated via local heat detection covering the generator. Upon activation of the detection system, a signal will be sent to the 24Vdc solenoid on the Nitrogen master cylinder. Nitrogen will be propelled into the water cylinders, forcing water at high pressure through the system pipe work and discharge as Watermist through all of the nozzles for the affected generator A double-knock heat & flame detection was also applied to this project.

NEED US URGENTLY?

For more information contact us on 01953 458420 or email enquiries@fireworks-ltd.com